Configuring the Gateway DFNT ♦ ProLinx Gateway
Protocol Manual EtherNet/IP Explicit Messaging Client/Server
Page 46 of 124 ProSoft Technology, Inc.
July 24, 2013
You may need to swap the order of the bytes in the registers during the copy
process in order to change the alignment of bytes between dissimilar protocols.
This parameter is helpful when dealing with floating-point or other multi-register
values, as there is no standard method of storage of these data types in slave
devices.
The following table defines the values and their associated operations:
No change is made in the byte ordering (1234 = 1234)
The words are swapped (1234=3412)
The words are swapped, then the bytes in each word are swapped (1234=4321)
The bytes in each word are swapped (1234=2143)