Ladder Logic MVI69-S3964R CompactLogix or MicroLogix Platform
Siemens 3964R Protocol
ProSoft Technology, Inc. Page 39 of 80
October 31, 2008
Click OK to continue.
4 Select the Request Packet Interval value for scanning the I/O on the module.
This value represents the minimum frequency the module will handle
scheduled events. This value should not be set to less than 1 millisecond.
Values between 1 and 10 milliseconds should work with most applications.
5 Save the module. Click OK to dismiss the dialog box. The Controller
Organization window now displays the module's presence. The following
illustration shows the Controller Organization window:
6 Copy the Controller Tags from the sample program.
7 Copy the User Defined Data Types from the sample program.
8 Copy the Ladder Rungs from the sample program.
9 Save and Download the new application to the controller and place the
processor in run mode.