QTS-CLX-APACS APACS® IOBUS Module User Manual
Page 4 QTS-CLX-APACS March 2015 Installation Prevent Electrostatic Discharge The module is sensitive to electrostatic discharge. WARNING! ATTE
QTS-CLX-APACS Page 5 You can install multiple QTS-CLX-APACS modules in the same chassis. Insert the Module in the Chassis The ControlLogix module i
Page 6 QTS-CLX-APACS March 2015 Figure 2 Inserting the Module Replacing a Module If you are replacing an existing module with an identical one, a
QTS-CLX-APACS Page 7 Cabling and Termination WARNING! Connecting the module disrupts bus traffic! Connect the module at a time when it is safe to do
Page 8 QTS-CLX-APACS March 2015 Configuring the Module in RSLogix 5000 You configure the module in RSLogix 5000 to set how much scheduled data to
QTS-CLX-APACS Page 9 2. Place another ENBT on the Ethernet under the first ENBT. Disable keying, set the Rack Connection to None,
Page 10 QTS-CLX-APACS March 2015 3. Place generic 1756-MODULEs in slots 0 to 9, as required. The configuration programs assign IO
QTS-CLX-APACS Page 11 Click OK Connection for REAL data Set the Comm Format to Data – REAL Set the Connection Parameters as shown. T
Page 12 QTS-CLX-APACS March 2015 Connection for Diagnostic Data Diagnostics are always mapped to connection 9. Connection 9 is not required but w
QTS-CLX-APACS Page 13 For example, you can use a longer RPI for the diagnostic data in connection 9, for example 500 milliseconds, since diagnostics
Page ii QTS-CLX-APACS March 2015 Because of the variety of uses for the products described in this publication, those responsible for the applica
Page 14 QTS-CLX-APACS March 2015 RSLinx When you right click on the module in RSLinx and select Properties, RSLinx displays the following: Parame
QTS-CLX-APACS Page 15 Monitor Mode Operation The following is a short summary of the steps typically followed. Refer to the appropriate manual sect
Page 16 QTS-CLX-APACS March 2015 Exporting a 4-mation database file The monitor configuration program uses a database file exported from the Sieme
QTS-CLX-APACS Page 17 Double click on each module and confirm that the channel types for that module are all present and correct.
Page 18 QTS-CLX-APACS March 2015 What gets mapped I/O Data APACS IOBUS discrete inputs and outputs are mapped to the input data o
QTS-CLX-APACS Page 19 Alias Name Offset Description StatBusANoiseErr 2 Bad packets, network noise StatFrameErr 3 Bad packets, framing errors S
Page 20 QTS-CLX-APACS March 2015 The QTS-CLX-APACS Module Properties dialog appears. Enter the Module Name. It can be up to 15 characters long.
QTS-CLX-APACS Page 21 TIP Use the same name that you assign the second ENBT module associated with the QTS-CLX-APACS in RSLogix 5000 to make it eas
Page 22 QTS-CLX-APACS March 2015 Configuring the QTS-CLX-APACS Module in RSLogix 5000. Follow the procedure on page 8 to configure the QTS-CLX-A
QTS-CLX-APACS Page 23 Enter the RSLinx Path Specifier to set the location of the module. This will be the name of the second ENBT module associate
Page 24 QTS-CLX-APACS March 2015 In this example, the module is in rack 1slot 6. The alias is for an analog input from channel 2 on the module, w
QTS-CLX-APACS Page 25 Using Monitor Mode for Migration You can use monitor mode on the QTS-CLX-APACS to migrate existing APACS applications to Contr
Page 26 QTS-CLX-APACS March 2015 and the corresponding alias in master mode ALIAS,"","APACS_AO_R01S06C01","APACS_AO_R01S0
QTS-CLX-APACS Page 27 Master Mode Operation WARNING! Never connect the APACS in master mode to the network while the ACM is controlling I/O. It tr
Page 28 QTS-CLX-APACS March 2015 ClxApacsMasCfg Software The QTS-CLX-APACS module is supplied with a Windows configuration tool, ClxApacsMasCfg.ex
QTS-CLX-APACS Page 29 Double click on each module and confirm that the channel types for that module are all present and correct.
Page 30 QTS-CLX-APACS March 2015 Assigning ControlLogix addresses Select Tools/Auto-allocate CLX Addressing to map the APACS IOBUS data to Control
QTS-CLX-APACS Page 31 Diagnostic Counters QTS-CLX-APACS diagnostic counters are integers and are mapped to ControlLogix input data of type INT on co
Page 32 QTS-CLX-APACS March 2015 TIP If the ControlLogix loses communication with the QTS-CLX-APACS, it sets the first four bytes of connection 0
QTS-CLX-APACS Page 33 Enter the Module Name. It can be up to 15 characters long. It should follow the rules for naming ControlLogix aliases; it s
QTS-CLX-APACS MODULE OVERVIEW 1 Part Number 2 Module Features 2 Power Requirements 3 Other Requirements 3 Package Contents 3 INSTALLATION 4
Page 34 QTS-CLX-APACS March 2015 If the ControlLogix processor with the connection to the QTS-CLX-APACS is in run mode when you download, the fo
QTS-CLX-APACS Page 35 The QTS-CLX-APACS Module Properties dialog box appears. It shows the required connections and the minimum connection sizes.
Page 36 QTS-CLX-APACS March 2015 Enter the RSLinx Path Specifier to set the location of the module. This will be the name of the second ENBT modu
QTS-CLX-APACS Page 37 In this example, the alias is for an analog output on channel 1 of the module in rack 1 slot 6, which is mapped to ControlLogi
Page 38 QTS-CLX-APACS March 2015 Accessing Data Required Connections In master mode, the QTS-CLX-APACS does not begin scanning the I/O bus until
QTS-CLX-APACS Page 39 In monitor mode, the bits do not update and are always 0. Aliases to the bits are provided by the configuration tool for comp
Page 40 QTS-CLX-APACS March 2015 Troubleshooting ControlLogix Module LEDs The module has three status LEDs to indicate the state of internal opera
QTS-CLX-APACS Page 41 OK LED – Module Health The OK LED indicates module health. A red LED indicates that module startup diagnostics have failed or
Page 42 QTS-CLX-APACS March 2015 If the module has no configuration, it refuses connection requests from the ControlLogix processor and returns a
QTS-CLX-APACS Page 43 for the bit associated with the module in rack 1 slot 4. Use the aliases to access the status bits. TIP If the ControlLogix lo
QTS-CLX-APACS Page iii Saving a Configuration File 21 Uploading and Downloading Configurations 21 Configuring the QTS-CLX-APACS Module in RSLogix
Page 44 QTS-CLX-APACS March 2015 Updating the Firmware The module firmware is updated using either of the two configuration programs. Copy the new
QTS-CLX-APACS Page 45 Specifications QTS-CLX-APACS ControlLogix Module Parameter Specification Module Location ControlLogix chassis Function Co
Page 46 QTS-CLX-APACS March 2015 Support How to Contact Us: Sales and Support Sales and Technical Support for this product are provided by ProSof
QTS-CLX-APACS Page 47 Warranty Quest Technical Solutions warrants its products to be free from defects in workmanship or material under normal use a
Page iv QTS-CLX-APACS March 2015 Program/Run 38 Diagnostic Data 38 TROUBLESHOOTING 40 ControlLogix Module LEDs 40 NET LED – IOBUS Status 40 C
QTS-CLX-APACS Module Overview The QTS-CLX-APACS connects a ControlLogix controller to an APACS® IOBUS network. Use the QTS-CLX-APACS
Page 2 QTS-CLX-APACS March 2015 Each I/O connection supports: • scheduled input data, 496 SINTs or 124 REALs • scheduled output data, 496 SINTs
QTS-CLX-APACS Page 3 Watchdog and Jabber Inhibit A watchdog timer is implemented in the module’s hardware. If the firmware does not kick the watchdo
Manuels d'utilisation et guides de l'utilisateur pour Non Home Decorators Collection 0191530.
Nous fournissons des manuels en pdf 1 Home Decorators Collection 0191530 à télécharger gratuitement par type de document : Manuel d'instructions
marque: Home-decorators-collection | Catégorie: No info | Taille: 0.92 MB |
Modèles | Type de document |
---|---|
1631810340 |
Manuel d'utilisation et d'entretien
![]() |
0463530960 |
Manuel d'instructions
![]() |
1540520310 |
Manuel d'utilisation et d'entretien
![]() |
1598300310 |
Manuel d'utilisation et d'entretien
![]() |
1296400880 |
Manuel d'utilisation et d'entretien
![]() |
1603260310 |
Manuel d'utilisation et d'entretien
![]() |
1774340950 |
Manuel d'utilisation et d'entretien
![]() |
1606000960 |
Manuel d'instructions
![]() |
0110425110 |
Manuel d'utilisation et d'entretien
![]() |
1844040610 |
Manuel d'utilisation et d'entretien
![]() |
0567300270 |
Manuel d'instructions
![]() |
1890120570 |
Manuel d'utilisation et d'entretien
![]() |
1296415210 |
Manuel d'utilisation et d'entretien
![]() |
1774320110 |
Manuel d'utilisation et d'entretien
![]() |
1315410400 |
Manuel d'utilisation et d'entretien
![]() |
2455300880 |
Manuel d'instructions
![]() |
0191358 |
Manuel d'instructions
![]() |
1740100210 |
Manuel d'instructions
![]() |
9084608 |
Manuel d'instructions
![]() |
0167320310 |
Manuel d'utilisation et d'entretien
![]() |
Kommentare zu diesen Handbüchern