Prosoft-technology MVI56E-DNPNET Bedienungsanleitung Seite 16

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 140
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 15
Contents MVI56E-DNPNET ControlLogix Platform
User Manual DNPNET Ethernet Client/Server Communication Module
Page 16 of 140 ProSoft Technology, Inc.
February 13, 2015
Parameter
Value
SLOT
Enter the slot number in the rack where the MVI56E-DNPNET
module is located
INPUT ASSEMBLY INSTANCE
1
INPUT SIZE
250
OUTPUT ASSEMBLY INSTANCE
2
OUTPUT SIZE
248
CONFIGURATION ASSEMBLY INSTANCE
4
CONFIGURATION SIZE
0
Important: You must select the COMM FORMAT as DATA - INT in the dialog box, otherwise the module will not
communicate over the backplane of the ControlLogix rack.
4 Click OK to continue.
5 Edit the Module Properties.
Select the REQUESTED PACKET INTERVAl value for scanning the I/O on the module. This
value represents the minimum frequency at which the module will handle scheduled
events. This value should not be set to less than 1 millisecond. The default value is 5
milliseconds. Values between 1 and 10 milliseconds should work with most applications.
Seitenansicht 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 139 140

Kommentare zu diesen Handbüchern

Keine Kommentare