MVI69-HART ♦ CompactLogix Platform Reference
HART Multi-drop Master Communication Module User Manual
ProSoft Technology, Inc. Page 139 of 169
March 29, 2012
COMMAND 44 - Write PV Units
Description
This command changes the setting of the Primary Variable units.
Write Parameters
Word High Byte Low Byte
0 Primary Variable Units Code Primary Variable Units Code
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Primary Variable Units Code 0