Prosoft-technology MVI69-MCM Bedienungsanleitung Seite 58

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 167
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 57
Configuring the MVI69-MCM Module MVI69-MCM ♦ CompactLogix or MicroLogix Platform
User Manual Modbus Communication Module
Page 58 of 167 ProSoft Technology, Inc.
March 22, 2011
Response Timeout
0
TO
65535 milliseconds
This parameter sets the command response timeout period in 1 millisecond
increments. This is the time that a port configured as a Master will wait for a
response from the addressed slave before re-transmitting the command (Retries)
or skipping to the next command in the Command List. The value to set depends
on the communication network used and the expected response time (plus a little
extra) of the slowest device on the network.
Retry Count
0 to 10
This parameter specifies the number of times a command will be retried if it fails.
Error Delay Counter
0 to
65535
This parameter specifies the number of polls to skip on the slave before trying to
re-establish communications. After the slave fails to respond, the Master will skip
commands to be sent to the slave the number of times entered in this parameter.