2 Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. Example: MVI69LMBS
Description
Enter a description for the module. Example: ProSoft
communication module for Serial Modbus communications.
Comm Format
Select Data-INT
Slot
Enter the slot number in the rack where the MV69E-MBS
module is installed.
Input Assembly Instance
101
Input Size
242
Output Assembly Instance
100
Output Size
241
Configuration Assembly Instance
102
Configuration Size
0
This module must be configured with a block transfer size of 240 words (input
block size = 242 words, output block size = 241 words):