Reference MVI71-MCM PLC Platform
Modbus Communication Module
ProSoft Technology, Inc. Page 93 of 111
December 28, 2007
This configuration will set the module to use a pre-defined time interval for
Modbus message recognition calculated for each baud rate. This should provide
optimal performance for most applications.
The following guard band timer values will be automatically used by the module
with the default parameter value (Guard Band Timer = 0) is selected:
Baud Guard Band Timer (ms)
110 350
150 256
300 128
600 64
1200 32
2400 16
4800 8
9600 4
19200 2
28800 2
38400 2
57600 1
115200 1
If you still observe a considerable number of communication errors, try to
increase the Guard Band Time value (in milliseconds) until the network
performance is improved.
5.6.4 Port 1 Commands
Register Content Description
5200 to 5207 Command #1
This set of registers contains the parameters for the
first command in the master command list. The
structure of this data area is as described in the
data object section of the documentation.
5210 to 5217 Command #2 Command #2 data set
- - -
6190 to 6197 Command #100 Command #100 data set
5.6.5 Port 2 Commands
Register Content Description
6400 to 6407 Command #1
This set of registers contains the parameters for the
first command in the master command list. The
structure of this data area is as described in the
data object section of the documentation.
6410 to 6417 Command #2 Command #2 data set
- - -
7390 to 7397 Command #100 Command #100 data set