Non Existing Slave Parameters
Execute download of configuration
database again.
Faulty Parameter Value in a Slave
Parameters
Check GSD file for possible incorrect slave
parameterization values.
Check configured slave addresses in
project.
Projected Send Process Data Offset
Address of a Slave is Outside the
Limits of 0 to 255
Check slave configuration in active project.
Projected Receive Process Data
Offset Address of a Slave is Outside
the Limits of 0 to 255
Check slave configuration in active project.
Data-Areas of Slaves are
Overlapping in the Send Process
Data
Check slave configuration in active project.
Data-Areas of Slaves are
Overlapping in the Receive Process
Data
Check slave configuration in active project.
Unknown Process Data Handshake
Problem with master’s startup parameters.
Master has a hardware issue.
Faulty Slave Parameter Dataset
Check GSD file for possible incorrect slave
parameterization datasets.
No Memory Segment Available
Master has a hardware issue.
Faulty Reading of a Database
Execute download of configuration
database again.
Structure Used by the Operating
System is Faulty
Master has a hardware issue.
Firmware watchdog has an error.
No Data Acknowledge in Process
Data Handshake
Firmware is having trouble with Host
acknowledgement.
The auto_clear mode was activated,
because one slave is missing during
runtime.
ERROR_EVENT Codes for an Err_Rem_ Adr of not equal to 255
Slave Station Reports Data
Overflow
Check length of configured slave parameter
or configuration data.
Request Function of Master is not
Supported in the Slave
Check if slave is PROFIBUS-DP norm
compatible.
No Answer, Although the Slave
must Respond with Data
Check configuration data of the slave and
compare it with the physical I/O data
length.
No Response from the Slave
Check bus cable, and bus address of slave.