
AN-X2-SQD-MAS Page 23
Offset Counter
4 UDP Tx Busy
5 UDP Rx Busy
Connection Statistics
The AN-X module maintains statistics for each scheduled connection.
The statistics for each connection consists of 10 words of data. Only three words in the
ten word block are used.
Offset Description
0 Average time for last 32 updates
2 Minimum time since the connection statistics were reset
4 Maximum time since the connection statistics were last reset
The units for the times are 0.1 milliseconds. A value of 87 means 8.7 ms.
Values update at a rate equal to 100 times the RPI for the connection. Averages are
calculated for the last 100 updates.
Resetting Connection Statistics
To reset the connection statistics, set bit 0 of output word 0 of connection 15. AN-X
resets the statistics on the transition from 0 to 1.
This does not reset the UDP diagnostics.
Example Configuration File:
;QTS AN-X SQD MAS Auto Configuration Utility
;Copyright (c) 2012 Quest Technical Solutions
;Auto Config Ethernet/IP File
ClxName Anx2SqdMas
ClxPrefix SQD_
LedModeDebug
ClxSlot 0
DataInput ; Inputs to ControlLogix
2 d1s02 ; 2->2 ( 1) "RIM101 16 IN AC/DC"
3 d1s03 ; 3->3 ( 1) "RIM101 16 IN AC/DC"
4 d1s04 ; 4->4 ( 1) "RIM101 16 IN AC/DC"
5 d8s09 ; 5->8 ( 4) "ROM121 4 OUT ANLG"
Kommentare zu diesen Handbüchern