5204SE-MNET-PDPMV1 ♦ ProLinx Gateway Reference
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master User Manual
Page 194 of 235 ProSoft Technology, Inc.
December 22, 2009
4.6 PROFIBUS Acyclic Telegram (Message) Block Structures
4.6.1 Set Operating Mode Message Structure
Parameter Description
Command Initiator Application
Command Name FB_APPL_SET_OPERATION_MODE
Command Number 0002h
Fragmented No
Extended Header Data Fault information may be returned in the header of the response.
Command and Response Layout: Set Operating Mode
Command Response
Message ID
(ID)
(ID)
Acyclic Message Status
Word
4002h
0002h
Command 0002h
0002h Set Operation Mode
Data size 0000h
0000h
Frame count 0001h
0001h
Frame number 0001h
0001h
Offset high 0000h
0000h
Offset low 0000h
0000h
Extended word 1 Req. Mode Conf. Req Act. Mode Conf. Req
Extended word 2 -
-
Extended word 3 -
-
Extended word 4 -
-
Extended word 5 -
-
Extended word 6 -
-
Extended word 7 -
Appl. Specific Error Code
Extended word 8 -
Fault Information
Mode
40h: STOP
80h: CLEAR
C0h: OPERATE
Conf. Req.
00h: Confirmation is not required
01h: Confirmation required. All confirmations are automatically sent by the
master, the user is not required to send a confirmation message.