7.1.2 Hardware Specifications
Specification
Description
Dimensions
Standard 1769 Single-slot module
Current Load
500 mA max @ 5 VDC
Power supply distance rating of 4 (L43 and L45
installations on first 2 slots of 1769 bus)
Operating Temp.
32° F to 140° F (0° C to 60°C)
Storage Temp.
-40° F to 185° F (-40° C to 85° C)
Relative Humidity
5% to 95% (with no condensation)
LED Indicators
Module OK Status
Backplane Activity
Ethernet Port Activity
Configuration Activity
CFG Port (ETH)
Diagnostics over Ethernet connection
App Ports (P1,P2)
RS-232, RS-485 or RS-422 (jumper selectable)
RJ45 Port (DB-9F with supplied cable)
500V Optical isolation from backplane
Shipped with Unit
DVD-001 Product DVD
RJ45 to DB-9M cables for each application port