MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
ProSoft Technology, Inc. Page 31 of 162
January 6, 2014
Note : The I/O Table Sizes above should reflect the Block Transfer Size parameter set in PCB
(Section 3.2 on page 53).
A Block Transfer Size of 60 uses an I/O Table Size of 62/61 words.
A Block Transfer Size of 120 uses an I/O Table Size of 122/121 words.
A Block Transfer Size of 240 uses an I/O Table Size of 242/241 words.
The MVI69E-MBS module is now visible at the I/O Configuration tree.
2.4.3 Creating a Module in the Project Using a Generic 1769 Module
Profile
1 Expand the I/O CONFIGURATION folder in the Project tree. Right-click the
appropriate communications bus and choose NEW MODULE.