AN-X-PBCAPT Page
25
149: a11.003,328,733 108<0 RFDL
150: a11.003,343,524 0<108 OK
151: a11.003,364,566 0<0
152: a11.003,381,530 1<0 SRDH 00
153: a11.003,404,488 0<1 DL 00
Source and Destination Nodes
To suppress the display of the destination node, include the NoDst option
line.
To suppress the display of the source node, include the NoSrc option
line.
Frames are shown with the destination node and source node separated
by a less than (<) sign. For example, the following frame has a source of
0 and a destination of 107:
146: a11.003,277,602 107<0 RFDL
The same frame with the destination node suppressed:
146: a11.003,277,602 <0 RFDL
with the source node suppressed:
146: a11.003,277,602 107< RFDL
and finally, with both destination and source node suppressed:
146: a11.003,277,602 RFDL
Frame Count Bit or Station Type
This corresponds to bits 4 and 5 in the the Control Octet in the Profibus
specification.
To display frame count bits for a request or station type for a response,
include the ShowFcbTyp option line.
On a command, the frame count bit alternates between 0 and 1. The
value is shown with a ‘v’ if the alternating function of the frame count bit
is valid and with a blank if it is not.
On a response, possible values are:
Station type Description
ss Slave station
mn Master station not ready to enter logical token ring
mr Master station ready to enter logical token ring