MVI56-PDPMV1 ♦ ControlLogix Platform Mailbox Messaging
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 141 of 255
March 22, 2011
The trigger bit is automatically reset when the message is enabled for execution:
When the mailbox is successfully executed, the counter ACC values will be
incremented:
MVI56PDPMV1.Util.MSG.MailboxRequest.DNCounter.ACC (Request)
MVI56PDPMV1.Util.MSG.MailboxResponse.DNCounter.ACC (Response)
When the mailbox execution was successfully performed, the mailbox response
will be stored in the controller tag structure
MVI56PDPMV1.Mailbox.GetSlaveConfig.In, which includes:
MVI56PDPMV1.Mailbox.GetSlaveConfig.In.ByteCount: number of identifier
bytes returned
MVI56PDPMV1.Mailbox.GetSlaveConfig.In.SlaveAddress: slave address
MVI56PDPMV1.Mailbox.GetSlaveConfig.In.ReturnCode: 0 if successful
MVI56PDPMV1.Mailbox.GetSlaveConfig.In.FaultInformation: 0 if successful