MVI71-DFNT PLC 5 Installing and Configuring the Module
EtherNet/IP Client/Server Communication Module User Manual
ProSoft Technology, Inc. Page 37 of 175
February 3, 2011
Parameter Range Description
Function Code See Command
Function Codes (page
34)
These parameters specify the function to be executed by the command. The
Reference chapter in this manual describes the meaning of these values for
each of the available supported commands. Following is a complete list of the
command supported by the Client driver.
Function Code Listing
Basic Command Set
1 Protected Write
2 Unprotected Read
3 Protected Bit Write
4 Unprotected Bit Write
5 Unprotected Write
PLC-5 Command Set (0x0F)
100 Word Range Write (Binary Address)
101 Word Range Read (Binary Address)
102 Read-Modify-Write (Binary Address)
150 Word Range Write (ASCII Address)
151 Word Range Read (ASCII Address)
152 Read-Modify-Write (ASCII Address)
SLC Command Set (0x0F)
501 Prot Typed Read with 2 addr fields
502 Prot Typed Read with 3 addr fields
509 Prot Typed Write with 2 addr fields
510 Prot Typed Write with 3 addr fields
511 Prot Type Write with Mask 3 addr field
Function
Parameters
See Command
Function Codes (page
34)
The number of auxiliary parameters required depends on the function code
selected for the command.