ILX34-AENWG POINT I/O Platform Procedures
Wireless Point I/O Adapter Setup Guide
Page 44 of 79 ProSoft Technology, Inc.
July 31, 2009
4 Click the C
ONNECTION tab, and then change the RPI value for the module
from 20 (the default) to 50 (the recommended value for analog or specialty
modules). This value determines how often to exchange data with the ILX34-
AENWG adapter.
Important: To avoid overloading the ILX34-AENWG adapter, we recommend that RPI be no less
than 10 ms for rack connections and 50 ms for direct connections.
5 Click OK save the configuration.
The following illustration shows the I/O Configuration for this project.