MVI56-DFCMR ♦ ControlLogix Platform Ladder Logic
DF1 Interface Module with Reduced Data Block
Page 42 of 113 ProSoft Technology, Inc.
October 20, 2008
3.3 Status Object (DFCMInStat)
This object views the status of the module. The DFCMInStat object shown below
is updated each time a read block is received by the processor. Use this data to
monitor the state of the module at a "real-time rate".
Name Data Type Description
PassCnt INT Program cycle counter
Product INT[2] Product Name
Rev INT[2] Revision Level Number
OP INT[2] Operating Level Number
Run INT[2] Run Number
PrtErrs DFCMPortErrors[2] Port error statistics
CmdReq INT Total number of command list requests sent
CmdResp INT Total number of command list responses received
CmdErr INT Total number of command list errors
Requests INT Total number of requests for port
Responses INT Total number of responses for port
ErrSent INT Total number of errors sent
ErrRec INT Total number of errors received
BlkErrs DFCMBlkStat Block transfer statistics
Read INT Total number of read block transfers
Write INT Total number of write block transfers
Parse INT Total number of blocks parsed
Event INT Total number of event blocks received
Cmd INT Total number of command blocks received
Err INT Total number of block transfer errors
P1CErr INT Port 1 current error/index
P1LErr INT Port 1 last error/index
P2CErr INT Port 2 current error/index
P2LErr INT Port 2 current error/index
Refer to Status Data Definition (page 85) for a complete listing of the data stored
in this object.