MVI69-DNP CompactLogix or MicroLogix Platform Configuring the MVI69-DNP Module
DNP 3.0 Master/Slave Communication Module
Page 30 of 129 ProSoft Technology, Inc.
November 3, 2008
Word Offset Definitions
5 Address in Slave
6 Point Count
7 DNP DB Address
8 IED DB Address
9 Poll Interval
The definition of each parameter required for each command is provided in the
following table.
Bits in the Port/Flags parameter are dependent on the data type. The following
table defines the Port/Flags bits for binary input, analog input and counter data
points.
Port/Flags Bits Description Decimal Equivalent
0 to 1 Communication port (0=Internal, 2=Port 2) 0 or 2
2 Enable/Disable Command (1=Enable, 0=Disable) 4
3 RBE Flag (0=Events from IED, 1=Events by module) 8
4 to 7 Not Used
For these data types the qualifier used in the data request is dependent on the
Point Count and Address in Slave fields in the command as follows:
If Point Count < 0, then use Qualifier 06h (All points, packed & -Point Count =
# of points to consider)
If Address in Slave = 0 & Point Count > 0, then use Qualifier 00h or 01h
(points 0 to Point Count -1)
If Address in Slave > 0 & Point Count > 0, then use Qualifier 00h or 01h
(Address in Slave to Address in Slave + Point Count - 1)
The following table defines the Port/Flags bits for binary output and analog output
points.
Port/Flags Bits Description Decimal Equivalent
0 to 1 Communication port (0=Internal, 2=Port 2) 0 or 2
2 Enable/Disable Command (1=Enable, 0=Disable) 4
3 Poll Type (0=Poll, 1=Exception) 8
4 Data Source (0=DNP Database, 1=IED Database) 16
5 to 7 Not Used
For these data types the qualifier used in the data request is dependent on the
Point Count and Address in Slave fields in the command as follows:
If Address in Slave = 0 & Point Count > 0, then use Qualifier 17h or 28h (Point
Count specified starting at point 0)
If Address in Slave > 0 & Point Count > 0, then use Qualifier 17h or28h (points
from Address in Slave to Address in Slave + Point Count - 1)
If Point Count <= 0, then ignore because this is illegal for outputs.
Digital input Digital input Events Digital Output Counter
0 Port/Flags Port/Flags Port/Flags Port/Flags
1 Slave Address Slave Address Slave Address Slave Address
2 1 2 12 20
3 0, 1 or 2 0, 1, 2 or 3 1* 0, 5 or 6
4 1* 1* 3, [4], 5 or 6 1, 7, 8, 9 or 10
5 Address in Slave Address in Slave Address in Slave Address in Slave