Reference PTQ-104S Rev2 Quantum Platform
User Manual IEC 60870-5-104 Server for Quantum
Page 182 of 195 ProSoft Technology, Inc.
February 22, 2013
Station Interrogation
(Station-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)
global
group 1 group 7 group 13
group 2 group 8 group l4
group 3 group 9 group 15
group 4 group 10 group 16
group 5 group 11
group 6 group 12
Clock synchronization
(Station-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)
Clock synchronization
Day of week used
RES1, GEN (time tag substituted/not substituted) used
SU-bit (summertime) used (Optional)
Command transmission
(Object-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)
Direct command transmission
Direct set point command transmission
Select and execute command
Select and execute set point command
C_SE_ACTTERM used
note 2
No additional definition
Short pulse duration (duration determined by a system parameter in the
outstation)
Long pulse duration (duration determined by a system parameter in the
outstation)
Persistent output
Supervision of maximum delay in command direction of commands and
set point commands
60 seconds Maximum allowable delay of commands and set point commands