2.1.17 [C_SE_NC_1 104]
This section defines the short-float setpoint database for the server emulated.
This information is sourced from the remote client and is transferred to the
database. If the Require Select parameter is set to one (1) or Y
ES, a Select
command must be received from the Client before an Execute command from
the Client will be processed.
This section takes the following parameters:
Point #:
DB Address:
Monitor Point #:
Monitor DB Addr:
Require Select:
Each point is two, 16-bit words and the DB Address value corresponds to the
double-word offset in the gateway memory database. For additional information
on how to set these parameters, see the 104S Tutorial and Reference chapters
of this manual.