Prosoft-technology 5201-MNET-101S Bedienungsanleitung Seite 119

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 159
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 118
IEC-101 Slave ProLinx Communication Gateway Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 119 of 159
August 6, 2010
Example 2 - Command Request with Response Only
For this example, the remote node is requesting the event buffer sizes from the
ProLinx gateway. This is an example of a request that requires a response back
from the gateway:
The following block can be used for the first request.
Command Request Block
Word Offset Database
Address
Value Description
0 3000 0 Block ID1 - Command Request Without Response
Move a value of 0 or any other value out of the 100
to 101 and 200 to 201 range, because no request
without response is performed
1 3001 202 Block ID2 - Command Request With Response.
2 to 98 3002 to 3098 Not Used Not Used
99 3099 0 Block ID1 - Command Request Without Response
Move a value of 0 or any other value out of the 100
to 101 and 200 to 201 range, because no request
without response is performed
Command Response Block
Word
Offset
Database
Address
Value Description
0 3100 202 Block ID2 - Command Request With Response.
1 3101 0 Block ID1 - Command Request Without Response
2 to 8 3102 to 3108 Event Buffers Event Buffers
99 3199 202 Block ID2 - Command Request With Response.
In order to send another command request to pass another event, use the
following format:
Seitenansicht 118
1 2 ... 114 115 116 117 118 119 120 121 122 123 124 ... 158 159

Kommentare zu diesen Handbüchern

Keine Kommentare