IEC-101 Slave ♦ ProLinx Communication Gateway 101S Protocol Configuration
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 45 of 159
August 6, 2010
2.9 [M_ME_NC_1]
This section defines the monitored short-float point database. This information is
sourced from the database and is transferred to the remote Master unit.
To determine the IOA (Information Object Address) for each object, add the
P
OINT # in the following section to the value of the M_ME_NC Parameter Offset
parameter set in the previous section.
This section takes the following parameters:
P
OINT #
DB
ADDRESS
G
ROUPS (page 50)
D
EFAULT DEADBAND
IV
DB BIT
Each point consumes four 8-bit bytes (two 16-bit words). The DB
ADDRESS value
corresponds to the double-word offset address in the database.
The DB
ADDRESS should be located in a database area that is being constantly
moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.
2.10 [M_IT_NA_1]
This section defines the monitored integrated totals (counter) database. This
information is sourced from the database and is transferred to the remote Master
unit. This section takes the following parameters:
P
OINT #
DB
ADDRESS
G
ROUPS (page 50)
IV
DB BIT
Each point consumes four 8-bit bytes (two 16-bit words). The DB
ADDRESS value
corresponds to the double-word offset address in the database.
The DB
ADDRESS should be located in a database area that is being constantly
moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.