Reference IEC-101 Slave ♦ ProLinx Communication Gateway
Protocol Manual IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Page 96 of 159 ProSoft Technology, Inc.
August 6, 2010
C_BO_NA
A Control 32-Bit Bitstring Command information object occupies two words and
uses double-word addressing.
For example, if you configured the following points:
These points would be used as follows:
Inf. Object Address Module Database Address
3100 Words 3000 and 3001 (Double-word address 1500)
600 Words 2000 and 2001(Double-word address 1000. Must
match the configuration of point 600 in M_BO_NA.)
3101 Words 3002 and 3003 (Double-word address 1501)
601 Words 2002 and 2001 (Double-word address 1001. Must
match the configuration of point 601 in M_BO_NA.)
3102 Words 3003 and 3004 (Double-word address 1502)
602 Words 2004 and 2005 (Double-word address 1002. Must
match the configuration of point 602 in M_BO_NA.)