AN-X-AMXRIO November 2011
Scheduled Data with a ControlLogix
AN-X-AMXRIO exchanges scheduled data with a ControlLogix processor.
It supports:
up to 248 registers of output data
up to 250 registers of input data
24 registers of status input data
The terms input and output are from the point of view of the ControlLogix.
The ControlLogix processor sends output data to the AN-X-AMXRIO and the AN-X
sends it out on the AutoMax Remote I/O network.
The AN-X receives input data from the AutoMax remote I/O network and sends input
and status input data to the ControlLogix.
There are two possible types of scheduled connections from the ControlLogix processor
to the AN-X-AMXRIO:
Exclusive owner connections, which contain input, output and status input
data
Input-only connections, which contain input and status input data
There can be only one exclusive owner connection to an AN-X module, but there can be
more than one input only connection to an AN-X.
To configure scheduled data exchange:
1. Configure AN-X in RSLogix 5000
2. Configure the remote I/O network in AN-X-AMXRIO
3. Use the tag conversion utility provided to create a tag file from the I/O
configuration
4. Import the tags into RSLogix 5000
Requirements
RSLogix 5000 version 12 or above
ControlLogix processor with version 12 or above firmware
100 Mbit Ethernet network and modules
Reference
Allen-Bradley publication EtherNet/IP Media Planning and Installation Manual,
publication ENET-IN001A-EN-P
WARNING!
Do not use the web interface to monitor data on the AN-X-AMXRIO