MVI46-DFNT ♦ SLC Platform Reference
EtherNet/IP Client/Server Communication Module User Manual
ProSoft Technology, Inc. Page 151 of 177
October 12, 2010
In order to complete the configuration of the MSG instruction, select the S
ETUP
SCREEN area of the MSG object. This displays the following dialog box.
Select the COMMUNICATION COMMAND to execute from the following list of
supported commands.
PLC5 Type Read
PLC2 Unprotected Read
PLC5 Typed Read to PLC
PLC Typed Logical Read
The TARGET DEVICE DATA TABLE ADDRESS must be set to a valid file element
(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Read
message, set the address to the database index (such as, 1000) to consider with
the command.
The M
ULTIHOP option must be set to YES. The MULTIHOP tab portion of the dialog
box must be completed as shown in the following window:
Set the IP address value to the module’s Ethernet IP address. You must press
the "Insert" key to add the second line for ControlLogix Backplane and set the
slot number to zero.