MVI46-DFCM SLC Platform Installing and Configuring the Module
DF1 Communication Module
Page 22 of 103 ProSoft Technology, Inc.
October 20, 2008
Register Range File Start File End Content Size
0 to 4999 N7:0 N31:199 User Data 5000
5000 to 5009 N32:0 N32:9 Backplane Configuration 10
5010 to 5039 N32:10 N32:39 Port 1 Setup 30
5040 to 5069 N32:40 N32:69 Port 2 Setup 30
5070 to 5199 N32:70 N32:199 Reserved 130
5200 to 6399 N33:0 N38:199 Port 1 Commands 1200
6400 to 7599 N39:0 N44:199 Port 2 Commands 1200
7600 to 7700 N45:0 N45:199 Misc. Status Data 200
7800 to 7999 N46:0 N46:199 Command Control 200
8000 to 9999 N47:0 N56:199 Reserved 2000
The user data areas hold data collected from other nodes on the network (master
read commands) or data received from the processor. Additionally, this data area
is used as a data source for the processor (read blocks) or other nodes on the
network (write commands).
2.2.1 Backplane Configuration
Database in SLC Database in MVI46-DFCM
File M0 Offset File Register Content Description
N10:0 1 N32:0 5000 Write Start Reg Not used in this version of the software
N10:1 2 N32:1 5001 Write Reg
Count
Not used in this version of the software
N10:2 3 N32:2 5002 Read Start Reg Not used in this version of the software
N10:3 4 N32:3 5003 Read Reg
Count
Not used in this version of the software
N10:4 5 N32:4 5004 Backplane Fail This parameter specifies the number of
successive transfer errors that must
occur before the communication ports
are shut down. If the parameter is set to
0, the communication ports will continue
to operate under all conditions. If the
value is set larger than 0 (1 to 65535),
communications will cease if the
specified number of failures occur.
N10:5 6 N32:5 5005 Error Status
Pointer
This parameter specifies the register
location in the module's database where
module status data will be stored. If a
value less than 0 is entered, the data will
not be stored in the database. If the
value specified is in the range of 0 to
4940, the data will be placed in the user
data area.
N/A N/A N32:6 5006 Spare Not used
N/A N/A N32:7 5007 Spare Not used
N/A N/A N32:8 5008 Spare Not used
N/A N/A N32:9 5009 Spare Not used