PLX8x-EIP-61850 Communication Gateway Configuring the PLX8x-EIP-61850 Gateway
Server to
IEC 61850 Client User Manual
ProSoft Technology, Inc. Page 29 of 167
July 2, 2015
2.10.2 Mapping Reports
Reports are based upon a DATA-SET, containing a specific collection of Data
Attributes. You can configure the gateway to enable an IED’s Buffered Report
Control Blocks (BRCBs) or Unbuffered Report Control Blocks (URCBs).
Note: Be sure that the DATA-SET on your IED contains all Data Attributes and not Data Objects.
1 In the Network View pane in the EIP-61850 Configuration Manager, right-click
the IED bubble that you want to map, and choose CONFIGURE.
This displays the IEC 61850 Mapping Tool window.
2 In the treeview on the left, expand (click the + sign) the root folder.
3 Expand (click the + sign) the Logical Device to see the Logical Nodes.
4 Continue to expand the Logical Node to display the Reports Object (RPT)
and finally the individual Reports.