PLX8x-EIP-61850 ♦ Communication Gateway Diagnostics and Troubleshooting
Server to
IEC 61850 Client User Manual
ProSoft Technology, Inc. Page 59 of 167
July 2, 2015
The PLC can read the value value by polling for the tag names
“EIPS_Connection_Status”, “IED_Node_Status”, or “Module_Driver_Status”
using a Class 3 MSG instruction as shown below (in RSLogix 5000).
The “Destination Element” of the RSLogix 5000 MSG instruction should be of
data type SINT.
Alternatively, you can configure a MSG instruction to poll for Class 0x300
Instance 0x01 and Attribute (as listed in the Class 3 MSGs tab). Below is a
sample MSG configuration using Class, Instance, Attribute messaging.
Again, the DESTINATION ELEMENT should be of data type SINT, and must contain
enough members based on the size of the data to obtain from the gateway.