5.1.3 Specifications - IEC 61850 Client
Supports up to 20 IEDs
Send commands from the PAC to the IED using Control Types
o Direct-with-Normal-Security
o Select Before Operate (SBO)-with-Normal-Security
o Direct-with-Normal-Security
o Select Before Operate (SBO)-with-Normal-Security
SCSM: IEC 61850 8.1(MMS) used
Generic substation event model (GSE)
Buffered Report Control Block (BRCB)
Unbuffered Report Control Block (URCB)
Direct-with-Normal-Security
SBO-with-Normal-Security
Direct-with-Enhanced-Security
SBO-with-Enhanced-Security
IEC 61850 Logical Nodes, including Logical Nodes
for Hydro Power Plants and Logical Nodes for
Wind Power Plants
Status available per node
Report and GOOSE status available
High-level status data available from Modbus
TCP/IP Client through the MNET server (for
example PLC or PAC)
5.1.4 Specifications - SNTP/NTP Client
The gateway supports a Simple Network Time Protocol (SNTP/NTP) client
service that can synchronize the gateway’s time by periodic update requests to a
Coordinated Universal Time (UTC) system. You can configure the SNTP/NTP
server details in ProSoft 61850 Configuration Manager. The resolution of the time
is in milliseconds (ms).
SNTP/NTP server synchronization rate
(in minutes)
SNTP/NTP server Address